2789-9052 – Modbus TCP/UDP communication module for Pro 2 power supplies
2789-9052 is a Modbus TCP/UDP Ethernet communication module for Wago Pro 2 power supplies. It makes the power supply's measured values, diagnostics and settings available on the automation network. The control system can monitor the voltage, current and operating status of the supply and adjust its parameters through the supported registers.
The integrated two-port Ethernet switch allows a line topology without a separate switch between each pair of devices. WBM and WebVisu provide browser access to configuration and data visualisation. The module attaches to the X4 interface of the Pro 2 power supply and also receives its power through this interface.
Main functions
- Modbus TCP and UDP: communication with the supervisory control system over Ethernet; Modbus UDP is available from module firmware 02.00.00.
- Power supply monitoring: monitoring of output voltage, current, load and status information, including overload and Boost functions.
- Power supply configuration: access to supported parameters, such as output voltage, signalling, warning thresholds and output mode.
- Web access: integrated WBM and WebVisu, HTTP/HTTPS communication; current firmware supports HTTPS with TLS 1.3.
- Two Ethernet ports: RJ45, 10/100 Mbit/s, integrated switch operating in store-and-forward mode.
- Network services: DHCP and SNTP; BootP from module firmware 02.00.00.
- Connection diagnostics: ERR and COM OK LEDs, with separate link activity and speed indication for both ports.
- Control cabinet labelling: slot for Wago WMB markers and marking strips.
Connection and firmware requirements
The module is designed for Pro 2 power supplies with firmware 01.04.xx or later. Older modules with firmware 01.00.03 must be updated as described in the manual before use with newer power supply firmware. Use current module firmware to access the full range of functions listed.
One communication module can be connected to each power supply. The power supply's communication interface provides 5 V DC, so no separate power supply is required. Connect Ethernet using shielded Cat 5e cable or higher; the maximum length of one segment is 100 m.
When using this module, the maximum operating temperature of the complete assembly is +55 °C, even if the power supply itself supports operation up to +70 °C.
Compatible Pro 2 power supplies
The module is designed to attach to the X4 communication interface of Pro 2 power supplies. It can be used with the following power supplies in our range, provided the firmware requirements are met:
- Single-phase 12 V DC power supplies: 2787-2134, 2787-2135.
- Single-phase 24 V DC power supplies: 2787-2144, 2787-2146, 2787-2147, 2787-2448.
- Single-phase 48 V DC power supplies: 2787-2154, 2787-2157.
- Three-phase 24 V DC power supplies: 2787-2344, 2787-2346, 2787-2347, 2787-2348.
- Three-phase 48 V DC power supplies: 2787-2357, 2787-2358.
- Redundant 24 V DC power supplies: 2787-3147/000-030, 2787-3448/000-030.
Technical data
- Communication protocols: Modbus TCP; Modbus UDP from firmware 02.00.00
- Ethernet: 2 × RJ45, 10/100 Mbit/s, full/half duplex
- Network cable: shielded Cat 5e or higher; maximum segment length 100 m
- Power supply: 5 V DC SELV via the power supply's communication interface
- Maximum current consumption: 250 mA
- Dimensions W × H × D: 35 × 80 × 22 mm; installed depth
- Weight: 45 g
- Degree of protection: IP20
- Operating temperature: −40 to +55 °C
- Storage temperature: −40 to +85 °C
- Relative humidity: 5–95%, non-condensing
The Pro 2 power supply and connection cables must be ordered separately.
Estimated delivery time: 6 - 10 days
Planning an order over €5,000?