WDP-Q KNX 123312-06 KNX master clock 230 V AC
Westerstrand WDP-Q KNX 123312-06 is a master clock for a common time throughout the building and scheduled control of KNX functions. It sends the time and date over the KNX bus and can also drive compatible secondary clocks via a separate pulse line. It is suitable for schools, office buildings, healthcare facilities and other premises where clocks in individual rooms need to show the same time.
The unit can simultaneously provide local time and UTC on separate group addresses. The regular transmission interval is set in ETS; the time can also be sent in response to a request from another device. Eight programmable KNX switching channels allow building functions to follow daily, weekly and calendar schedules.
Synchronisation and time schedules
The unit uses a precise quartz time base. For external synchronisation, a compatible GPS or DCF receiver can be connected, or the time can be received from another source via KNX. The GPS/DCF receiver is ordered separately according to the project requirements. Automatic switching between summer and winter time and a preprogrammed calendar simplify operation of the clock system throughout the year.
- The time and date are transmitted in the combined DPT 19.001 format or separately as time DPT 10.001 and date DPT 11.001.
- Cyclic time transmission is adjustable from 1–1 440 minutes; the unit also supports responses to time requests.
- Eight KNX switching channels send commands according to time schedules. The loads are controlled by downstream KNX actuators.
- Six buttons and a two-line display with 16 characters per line provide schedule programming and local operation.
- A separate pulse output allows compatible clocks to be synchronised using minute or second pulses.
Time recovery after a power failure
The internal clock and pulse memory retain the time state for up to 72 hours. If power is restored within this period, the unit automatically corrects the connected clocks. This function restores the correct time; it does not provide backup power to the entire clock system during an outage.
Technical specifications
- Order number: 123312-06.
- Communication: KNX TP.
- Power supply: 230 V AC, 50 Hz, tolerance −5 % / +10 %.
- Maximum power consumption: 30 W, depending on the pulse output load.
- KNX bus current consumption: 10 mA; SELV 29 V DC connection.
- Time base accuracy: 0.1 s per 24 hours at +20 °C.
- Switching channels: 8 KNX communication channels.
- Physical pulse output: 1; max. 1 A with minute pulses or 0.5 A with second pulses.
- Pulse output protection: automatically resetting short-circuit protection.
- Pulse memory: 72 hours.
- Dimensions (W × H × D): 190 × 160 × 103 mm.
- Construction: light grey plastic housing with a transparent protective cover.
- Mounting: indoor wall mounting.
- IP rating: IP20.
- Operating temperature: 0 to +40 °C.
System connection
WDP-Q KNX requires a 230 V AC mains supply and a connection to a powered KNX bus. Group addresses and the method of time transmission are configured in ETS. The bus can be connected to KNX wall clocks without a second hand or clocks with a sweeping second hand. System planning must account for the total current drawn by the devices from the bus and the load on any pulse line.
Documentation
WDP-Q KNX datasheet (PDF, EN)
Installation and operating instructions (PDF, EN)
Estimated delivery time: 10 - 18 days